90
10 Correcting Faults
10.1.3 Error codes at the level of the operating unit
Warning EEPROM writing error
– Exchange device
100 Periodic signal <47 Hz- Warning strong resonance in burner chamber
other internal error
No. Description
Communication error
No. Description Graphic W *
C0001 Timeout - X
At secure parameter transfer, the F300K did not respond within the safety time; in other
words, the parameters were not accepted by the F300K.
C0002 Communication X
The F300K is no longer responding.
F300K is no longer reachable Bus improperly terminated, line lengthtoo long, interfer-
ence, defect or missing power supply
C0003 Memory --
Error reading from/writing to flash memory
Repeat the operation or device defective
C0004 Communication --
BUS error
If this error occurs repeatedly, change the user interface or have a repair carried out.
C0005 Communication --
BUS error
If this error occurs repeatedly, change the user interface or have a repair carried out.
C0006 No access level - X
The access level has been reset.
The time has expired.
Enter the password again.
C0007 Communication --
If this error occurs repeatedly, change the user interface or have a repair carried out.
C0008 Multiple devices are connected. - -
An external user interface has been detected.
It is no longer possible to operate the device using the internal user interface.
The external user interface has a connection to the F300K. Dual operation is pre-
vented.
C0009 Multiple devices are connected. - -
It is not possible to operate the device with either the internal or the external user inter-
face.
The F300K Remote Software has a connection to the F300K. Dual operation is pre-
vented.
C0010 Multiple devices are connected. - -
Two external user interfaces have been detected on the bus.
Remove one of the external user interfaces from the bus.
C0011 Multiple devices are connected. - -