10 Correcting Faults
10 Correcting Faults
10.1 Fault Finding and Troubleshooting
10.1.1 Commissioning
Cable types and cross sections to be used
Shielded cables e.g. LiYCY
Cross-section:> = 0.5 mm
2
, 20 AWG
NOTICE
The maximum length of the FSB is 80 m (both directions); for length> 80 m, intermediate am-
plifiers (repeaters) must be used.
Problem Possible cause Remedy
No Bus communica-
tion via the main con-
necting cable
Bus is not correctly termi-
nated.
F300K with user interface
Use the User Interface to switch the terminating
resistor on.
F300K
Use a connecting cable that is as short as possible.
Termination: Connect a 120 terminating resistor to
the last device connected to the bus.
Switch the terminating resistor on again in the
F300K.
External User Interface
Switch on the terminating resistor with the external
User Interface (7.6.2 Parameterising the User Inter-
face
USB/FSB module
Add the terminating resistor.
Installation, commissioning, maintenance
Note the document "supply and engineering guide".
Fig. 10-1 CAN bus termination
The error LED
flashes constantly
although the error
has been eliminated
and/or an error can-
not be read out.
A serious error has occurred
resulting in the prevention of
an automatic RESET.
Reset the hardware by interrupting the supply volt-
age for approximately 10 seconds.
Read the error out after switching the device on
again.
If the error occurs again, contact the manufacturer.