97
14 Appendix
14 Appendix
14.1 Technical Data
14.1.1 F300K
NOTICE
Note that the F300K connection plug in stainless steel design has a different plug code.
You will need the connection cable for F300K in stainless steel design.
Fig. 14-1 Dimensioned drawing of the F300K
* Comparative evaluation from 1 (very good) to 6 (unsuitable)
1
The product must not be transported, stored or operated outside the specified range. If it is, any guarantees with regard to safety-
related functions lose their validity.
Housing
Material Corrosion-resistant aluminium EN AW 6082 (seawater 2*;
atmospheric condition 1*), anodised or stainless steel
Dimensions 195,5 x 99 mm/3.9"x7.7" in
Weight 1.05 kg/2.3 lb in Al,
3,6 kg/7.9 lb in stainless steel V4A
Input parameters
Auxiliary power
Supply voltage
1
24 VDC ± 20%
Power consumption 3.7 W
Digital inputs – mode switching
Control voltage
1
24 VDC ± 20%
Control current Approx. 6 mA
Signal input
Responsiveness 18 mVAC