9 Repairs
9 Repairs
When the F300K is replaced, it is necessary to replace it with a device with the same identifi-
cation information.
If possible, the parameterisation can be taken from the defective device, a backup file see
chapter 7.5.4 Save parameters (down load) (down load) or the commissioning log. Any cus-
tomisation of safety-related parameters that is necessary will be focused on the switching
threshold. See chapter7.4 Automatic setting and 7.5 Manual setting
NOTICE
The correct parameterisation after data transfer and parameter adjustment have to be verified
through switch-off tests see section 6.4.5 Switch-off Test