Electrical installation − HighLine/StateLine version
Safety engineering
6
103
EDS84DPS424 EN 5.0
X61 − connection of safety system "Safety Option 10"
Pin Connection Description Data
M12, 5−pole pins, A−coded
84DPSO05_5
1 SIA Safe input, channel A
I
typ
= 45 mA
LOW: −3 ... 5 V
HIGH: 18 ... 30 V
Supply through safely
separated power supply unit
(SELV/PELV).
2 SIB Safe input, channel, B
5 GI 1. GND potential for SIA/SIB
2. GND potential for the non−safe signalling
output
24 V, max. 0.2 A
short−circuit−proof
Supply through safely
separated power supply unit
(SELV/PELV).
High active
4 24O 24−V voltage supply for the non−safe signalling
output
3 DO1 Non−safe signalling output: "SafeTorqueOff"
with 2−channel request by SIA and SIB

Table of Contents