Electrical installation − HighLine/StateLine version
Safety engineering
6
104
EDS84DPS424 EN 5.0
X62 − connection of safety engineering system "Safety Option 30"
Pin Connection Description Data
M12, 5−pole sockets, A−coded
84DPSO05_5
1 AIE Error acknowledgement
2 24_ACK 24−V supply voltage for reset button max. 300 mA
3 AIS Restart acknowledgement
4 GND_SM
GND potential
5 GND_SM
X63 − connection of the "Safety Option 30" safety engineering system
Pin Connection Description Data
M12, sockets 8−pole, A−coded
84DSO05_8
1 CLA Clock output, channel A
2 CLB Clock output, channel B
3 GND_CLK GND potential − clock output, channel A
4 I1A Safe input 1, channel A
5 GND_I1 GND potential − input 1, channel A
6 I1B Safe input 1, channel B
7 GND_CLK GND potential − clock output, channel B
8 GND_I1 GND potential − input 1, channel B
X64 − connection of the "Safety Option 30" safety engineering system
Pin Connection Description Data
M12, sockets 8−pole, A−coded
84DSO05_8
1 CLA Clock output, channel A
2 CLB Clock output, channel B
3 GND_CLK GND potential − clock output, channel A
4 I2A Safe input 2, channel A
5 GND_I2 GND potential − input 2, channel A
6 I2B Safe input 2, channel B
7 GND_CLK GND potential − clock output, channel B
8 GND_I2 GND potential − input 2, channel B