EasyManua.ls Logo

Lenze i700

Lenze i700
359 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 Motor control & motor settings
5.10 Synchronous motor (SM): Pole position identification
111
Lenze · i700 servo inverter · reference manual · DMS 3.0 EN · 06/2016 · TD06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Subindex 1: PPI (min. movement): Current amplitude
Adjustment of the current amplitude in percent
For large machines and high mass inertia values or for linear direct drives, the current amplitude usually has to
be increased.
A Lenze setting of "100 %" corresponds to 35 % of the rated motor current (0x6075
or 0x6875 for axis B).
Note!
If the current amplitude is set to > 400 %, the device utilisation (Ixt) monitoring and/or one of the motor monitoring
functions may respond and cause the abort of the pole position identification.
Setting range (min. value | unit | max. value) Lenze setting
1 % 1000 25 %
Write access CINH OSC P RX TX UNSIGNED_16
Subindex 2: PPI (min. movement): Ramp time - current
Adjustment of the rate of rise of the current in percent
Setting range (min. value | unit | max. value) Lenze setting
1 s 600 10 s
Write access CINH OSC P RX TX UNSIGNED_16
Subindex 3: PPI (min. movement): Gain
Adjustment of the proportional gain of the PI controller
With the Lenze setting "0", the PI controller works as an I-controller.
Setting range (min. value | unit | max. value) Lenze setting
0 % 1000 0 %
Write access CINH OSC P RX TX UNSIGNED_16
Subindex 4: PPI (min. movement): Reset time
Adjustment of the PI controller reset time
For this, observe the following setting details:
In order to be able to compensate a positional variation faster, first the reset time should be reduced. If this
does not result in the desired behaviour, the proportional gain can be increased.
Ensure that the position control does not get unstable. We therefore recommend to use an I controller.
Setting range (min. value | unit | max. value) Lenze setting
0.1 ms 6000.0 62.5 ms
Write access CINH OSC P RX TX Scaling: 1/10 UNSIGNED_16
Subindex 5: PPI (min. movement): Max. move permitted
Adjustment of the permitted movement
The pole position identification comprises a monitoring function for the follow-up control. If a movement
greater than the permissible movement set is detected by the encoder system, the pole position identification is
aborted and the error response parameterised is tripped:
In order to detect a non-permissible blocking of the machine, a positive and negative test angle relative to the
current position are defined after the identification. The machine must align itself to these two test angles
within a tolerance of 25 %. The size of the test angle corresponds to the max. move permitted set here.
Setting range (min. value | unit | max. value) Lenze setting
1 ° 90 20 °
Write access CINH OSC P RX TX UNSIGNED_8

Table of Contents

Other manuals for Lenze i700

Related product manuals