7 CiA402 device profile
7.4 Device control
189
Lenze · i700 servo inverter · reference manual · DMS 3.0 EN · 06/2016 · TD06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7.4.1.7 Fault reset
From all states
Power section inhibited (pulse inhibit)
Power section enabled
This command serves to reset an existing fault
if the cause of the fault has been eliminated.
The pulse inhibit remains set.
A changeover to the "Switch on disabled
"
device status takes place, i. e. the switch on
inhibit is active.
Bit pattern for the "Reset fault" in the Controlword (0x6040 or 0x6840 for axis B):
Bits 15 - 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Fault reset Control bits depending on the operating mode Enable
operation
Activate quick
stop
Enable voltage Switching on
X0 1 X X XXXXX
1
2
0
Ready to
switch on
Not ready to
switch on
Switched
on
Operation
enabled
Fault reaction
active
Fault
Switch-on
disabled
Quick stop
active
Power-on