Technical data
Leuze electronic RSL 430 119
15.4 Representation of safety sensor status
The table lists all logic and electrical signals that are present in the safety sensor. The signal names are
used consistently throughout the configuration and diagnostics software (device DTM), in the event log and
in the data telegram.
Tab.15.16: Status profile
Byte Bit Signal Description Value "0" Value "1" Default
0 --- --- Type (model) of status profile.
Extensions require new type of
status profile
--- --- 1
1 --- OP-MODE Operating mode:
• 1: Safety mode
• 2: Simulation mode
--- --- 1
Messages and OSSDs
2 7 ERROR Collective message:
Error with switch-off
off message 0
6 ALARM Collective message:
Warnings with switch-off (also win-
dow warning)
off message 0
5 SCREEN Contamination display for optics
cover
Warning and switch-off
off message 0
4 EDM EDM collection error off message ---
3 FIELDPAIR Collective message:
Fault detected by field pair selec-
tion monitoring
off message ---
2 E-STOP Error with OSSD linkage / E-Stop
monitoring
off message ---
1 A-OSSD OSSD state
Protective functionA
off on 0
0 B-OSSD OSSD state
Protective functionB
off on 0
Emergency stop and parking
3 7 Status-Input-SE Status of the inputs SE1 and SE2
E-STOP
off on 0
6 Mode-PARK Park request fulfilled off parked 0
5 Reserved --- --- --- 0
4 Reserved --- --- --- ---
3 Reserved --- --- --- ---
2 Reserved --- --- --- ---
1 Reserved --- --- --- ---
0 Reserved --- --- --- ---