Configuring the safety sensor
Leuze electronic RSL 430 86
9.7 Saving configuration
To save the changed configuration loaded in the software, you can transfer the configuration and settings
to the safety sensor or save them in a file on the PC.
Saving safety configuration as PDF file
Ä In the CONFIGURATION menu, click the [Create PDF file of safety configuration] button.
Ä Determine the storage location and the file name for the safety configuration.
Ä Click [Save].
ð The safety configuration is saved as a PDF file.
Saving configuration and settings as file
Ä In the CONFIGURATION menu or in the SETTINGS menu, click the [Save configuration and settings to
file] button.
Ä Determine the storage location and the name of the configuration file.
Ä Click [Save].
ð The configuration and settings are saved in the file format *.xml.
Saving configuration project as file
Ä In the menu bar of the FDT frame menu, click the button.
Alternatively, select the menu command File > Save.
Ä Determine the storage location and the name of the configuration project file.
Ä Click [Save].
9.8 Transferring configuration project to safety sensor
The changes that you have made to the configuration only become effective when the changed configura-
tion project file is transferred to the safety sensor.
Prerequisites:
The software and safety sensor are connected.
The changed configuration project has been loaded in the software.
The individual password for the access level Engineer is available.
Only users with the access level Engineer can transfer configuration data to the safety sensor. To
change the access level, see chapter 9.9 "Selecting access level".
If no individual password has been defined for the access level Engineer, use the preset default
password (safety).
NOTICE
Alternatively, you can transfer a configuration project saved as a file on the PC directly to the
safety sensor.
Ä In the menu bar of the FDT frame menu, click the [download arrow] button. Alternatively: In the FDT
menu bar, select Device > Download parameters.
ð The software asks for the access level and the password.
Ä Select the access level Engineer and enter the preset default password (safety) or the defined individ-
ual password.
Confirm with [OK].