Configuring the safety sensor
Leuze electronic RSL 430 85
9.5 Defining permissible field pair changeovers
If monitoring of field pair changeover is activated, you can define the permissible sequence of field pair
changeovers.
Determining changeover mode
Ä In the CONFIGURATION menu, select the protective functionA or protective functionB option.
Ä In the dialog box MODE FOR FIELD PAIR ACTIVATION AND CHANGEOVER, select the field pair ac-
tivation, the mode for field pair changeover and, if required, the changeover time.
Field pair activation
Changeover mode
Description
Fixed selection of one field
pair
Changeover of two field pairs
Selection by signal inputs
Fixed changeover moment
Changeover of 10 field pairs (see chapter 5.7.3 "Changeover of ten field
pairs in changeover mode Fixed changeover moment")
When the changeover time has expired, the system changes over to the field
pair which at this time has a permanent and valid assignment. Field pair
changeover signals issued during the changeover time are ignored.
The inputs F1 - F5 are active.
The inputs F6 - F10 are active.
Selection by signal inputs
Overlapped monitoring
Changeover of 5 field pairs (see chapter 5.7.2 "Changeover of five field pairs
in changeover mode Overlapped monitoring")
Both field pairs are monitored during the changeover time.
The inputs F1 - F5 are active.
The inputs F6 - F10 are active.
Ä Click the [Confirm] button.
Determining changeover order
Ä In the CONFIGURATION menu, select the Changeover order option.
ð The CHANGEOVER ORDER dialog box opens.
Ä In the MONITORING OF FIELD PAIR CHANGEOVER dialog box, activate the Monitoring option.
Ä In the MONITORING OF FIELD PAIR CHANGEOVER dialog box, define the sequence of field pair
changeovers according to your conditions.
Ä Click the [Confirm] button.
9.6 Configuring signal outputs
You can define which indication signals are transmitted to the individual indication signal connections.
Ä In the CONFIGURATION menu, select the Outputs option.
The OUTPUTS dialog box opens.
Ä For each usable connection, select the function group and the function of the indication signal.
Ä Click the [Confirm] button.
NOTICE
All signal outputs are high active, i.e. logical 1 or +24V DC with an active signal.