Functions
Leuze electronic RSL 430 34
5.2.3
One protective function – four field mode
The safety sensor monitors one protective field and three warning fields.
Monitoring is performed together for the field pairs of protective functionA and protective functionB. If, for
example, the control system is monitoring field pair A1.1 for protective functionA, field pair B1.1 for protec-
tive functionB is also monitored.
1 Protective function A: protective field
2 Protective function B: protective field
3 Protective function A: warning field
4 Protective function B: warning field
Fig.5.1: Four field mode
If the protective field of protective functionA is violated, safety-related switching outputs OSSD-A switch.
If the protective field of protective functionB is violated, the indication signal B-CLEAR is generated – the
safety-related switching outputs do not switch.
The signals are assigned to the switching outputs via the configuration and diagnostics software (CONFIG-
URATION > Outputs; see chapter 9 "Configuring the safety sensor").
Tab.5.3: Example: Assignment of signals to switching outputs
Logic signal Electrical switching output Description
OSSDA Safety-related switching outputs OSSDA Protective functionA: protective field violation
B-CLEAR Switching output MELD – not safe Protective functionB: protective field violation
A-WF-VIO Switching output A1 Protective functionA: Violation of warning field
B-WF-VIO Switching output EA1 Protective functionB: Violation of warning field