Starting up the device
Leuze electronic RSL 430 91
Transferring configuration with the PC
If the range and/or performance class of the replacement scanner unit is not compatible with the original
scanner unit, you must adapt the configuration of the safety sensor to the replacement scanner unit.
Ä Connect the safety sensor's Ethernet communication interface with the PC.
Ä Configure the safety sensor according to the range and performance class of the replacement scanner
unit (see chapter 9 "Configuring the safety sensor").
Ä Transfer the configuration to the safety sensor with the replacement scanner unit.
ð The alphanumerical display confirms successful transfer of the configuration.
The replacement scanner unit is not compatible with the connection unit if the safety sensor displays a
fault.
Checking replacement scanner unit
The check performed on the replacement device depends on whether you automatically adopted the con-
figuration from the connection unit or whether you transferred the changed configuration to the safety sen-
sor.
Ä If you adopted the configuration from the connection unit, check the safety sensor using the checklist
for the daily test.
Ä If you transferred a new configuration to the safety sensor, check the safety sensor according to the
routine for initial start-up (see chapter 11.1.1 "Checklist for integrator – to be performed prior to the ini-
tial start-up and following modifications").