Vertiv | Liebert® GXT5™ | Installer/User Guide 119
Table 7-12 Battery Run Time, 1500 VA Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6 7 8 9 10
% VA W Minutes
10 150 150 107.3 350.3 612.3 885.6 1173.2 1436.2 1644.5 1797.2 1914.0 2006.2 2080.9
20 300 300 52.8 187.9 325.3 472.1 618.0 769.6 927.7 1089.0 1247.1 1393.8 1526.8
30 450 450 32.7 123.9 213.1 309.0 407.6 508.2 609.2 708.8 815.3 923.4 1033.0
40 600 600 22.2 89.2 159.1 226.4 297.8 371.9 448.5 523.5 600.5 672.1 751.6
50 750 750 16.3 70.2 125.3 179.9 234.5 292.4 351.5 411.5 472.8 533.9 596.2
60 900 900 12.7 55.1 103.5 148.3 194.8 239.7 289.0 338.1 387.8 439.9 489.9
70 1050 1050 10.1 44.5 85.9 125.6 165.6 203.4 243.0 285.0 326.6 369.5 412.5
80 1200 1200 8.2 38.6 73.8 108.4 142.3 176.3 208.4 244.0 280.4 316.9 353.6
90 1350 1350 6.7 32.7 61.7 93.2 124.1 154.3 184.8 213.4 245.0 277.0 309.4
100 1500 1500 5.6 28.2 54.3 83.4 111.2 138.5 165.8 192.5 218.4 246.7 275.3
Table 7-13 Battery Run Time, 2000 VA Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6 7 8 9 10
% VA W Minutes
10 200 200 78.5 258.8 455.3 650.5 861.7 1078.7 1289.4 1482.1 1636.0 1757.5 1855.8
20 400 400 36.2 134.8 231.0 334.0 442.2 550.0 653.9 767.6 883.1 1000.1 1118.7
30 600 600 21.8 88.2 156.6 223.1 293.8 366.4 441.9 515.7 592.1 662.0 740.7
40 800 800 14.8 63.1 115.9 167.7 216.8 269.8 324.8 380.4 437.8 493.7 551.2
50 1000 1000 10.7 47.1 89.2 131.9 172.7 211.1 254.6 297.4 341.8 386.1 432.1
60 1200 1200 8.2 38.5 73.5 108.1 141.9 175.8 208.0 243.2 279.6 316.0 352.7
70 1400 1400 6.3 31.0 58.9 89.2 119.1 148.5 178.3 206.2 236.1 266.8 297.8
80 1600 1600 5.0 25.9 50.1 78.1 103.9 129.3 154.3 179.9 204.6 230.7 257.6
90 1800 1800 4.0 22.0 42.9 66.5 88.9 113.0 136.0 158.2 180.4 202.5 225.2
100 2000 2000 3.2 18.8 38.1 57.1 79.8 99.9 119.3 140.7 161.0 180.6 200.6