EasyManuals Logo

Liebert Vertiv GXT5 User Manual

Liebert Vertiv GXT5
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #126 background imageLoading...
Page #126 background image
Specications118
7.1. Battery Run Times
Run times in this table are approximate. Times are based on new, fully-charged, standard battery mod-
ules at a temperature of 77 °F (25 °C) with 100% resistive UPS loading. Run times listed above can vary
by ±5% due to manufacturing variances of the individual batteries.
Table 7-10 Battery Run Time, 750 VA Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6 7 8 9 10
% VA W Minutes
10 75 75 135.4 444.1 770.8 1123.4 1452.2 1695.4 1863.8 1987.3 2081.7 2156.3 2216.6
20 150 150 68.0 229.0 401.4 581.6 760.5 952.0 1147.8 1330.7 1499.7 1635.5 1745.4
30 225 225 44.1 163.7 281.7 407.9 537.8 663.9 800.6 939.7 1080.9 1221.8 1350.2
40 300 300 33.7 127.1 218.3 316.1 416.5 519.9 620.3 724.8 833.9 944.6 1056.5
50 375 375 25.7 103.2 178.9 255.9 337.1 420.2 505.5 592.1 672.6 761.7 852.0
60 450 450 20.4 84.8 149.0 212.4 280.7 350.0 420.3 492.6 565.3 631.7 706.8
70 525 525 16.7 72.0 128.2 183.8 238.8 298.1 358.3 419.6 481.8 544.9 607.0
80 600 600 14.1 59.7 112.1 161.6 208.6 260.6 313.2 366.4 420.4 475.8 531.1
90 675 675 12.1 53.0 99.5 143.9 188.3 232.1 278.8 326.1 374.6 423.3 473.1
100 750 750 10.5 46.3 88.3 130.2 170.8 208.8 251.5 294.1 337.6 381.7 426.5
Table 7-11 Battery Run Time, 1000 VA Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6 7 8 9 10
% VA W Minutes
10 100 100 101.8 332.7 584.9 841.2 1114.7 1373.2 1590.9 1750.8 1873.0 1969.6 2047.7
20 200 200 50.1 179.8 311.9 453.2 595.8 736.7 888.2 1042.4 1199.1 1340.5 1476.5
30 300 300 33.7 127.1 218.3 316.1 416.5 519.9 620.3 724.8 833.9 944.6 1056.5
40 400 400 23.8 95.8 168.9 239.3 316.4 394.3 474.5 555.3 629.9 713.6 798.3
50 500 500 17.8 76.3 135.1 193.0 251.8 314.0 377.3 443.1 506.8 573.0 632.6
60 600 600 14.1 59.7 112.1 161.6 208.6 260.6 313.2 366.4 420.4 475.8 531.1
70 700 700 11.5 50.7 95.3 139.4 181.7 224.1 268.6 315.0 361.0 408.6 457.6
80 800 800 9.6 43.3 83.4 120.8 160.1 197.6 235.3 275.3 316.3 357.1 399.0
90 900 900 8.1 38.2 73.0 107.4 141.0 174.8 206.9 241.5 277.6 314.0 350.4
100 1000 1000 6.8 33.3 62.8 94.6 125.7 156.3 187.0 216.1 248.0 280.4 313.1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Liebert Vertiv GXT5 and is the answer not in the manual?

Liebert Vertiv GXT5 Specifications

General IconGeneral
Output Voltage230V
TopologyDouble Conversion Online
Frequency50/60 Hz
Operating Temperature0°C to 40°C
DimensionsVaries by model
WeightVaries by model
Form FactorRack/Tower
Battery TypeValve Regulated Lead Acid (VRLA)
Communication PortsUSB, RS-232
EfficiencyUp to 95%
Typical Recharge Time3 hours to 90%
Storage Temperature-15°C to 40°C
Humidity0% to 95% non-condensing

Related product manuals