Vertiv | Liebert® GXT5™ | Installer/User Guide 69
Outlet settings based on backup time
Threshold of turning o the outlet
When the selected amount of time remains on battery mode, the outlet is turned off. Select
the checkbox to enable or disable (default) the option.
• 0 to 30 minutes (default is 5)
Turn on when power returns for
Length of time after the mains input power returns before turning on the outlet. Select the checkbox
to enable or disable (default) the option.
• 0 to 30 minutes (default is 0)
Outlet settings based on capacity
Threshold of turning o the outlet
When the selected percentage of capacity remains in battery mode, the outlet turns off. Select the
checkbox to enable or disable (default) the option.
• 20 to 80% (default is 20%)
Turn on when power returns
Length of time after the mains input power returns before turning on the outlet. Select the checkbox to
enable or disable (default) the option.
• 0 to 30 minutes (default is 0)
4.2.5. Control Screen
The Control Screen offers UPS-control options.
To adjust the UPS controls:
1. At the main menu, select the Control icon, and press Enter.
2. Use the arrow buttons to move the cursor to the option, then press Enter to select the control.