EasyManuals Logo

Liebert Vertiv GXT5 User Manual

Liebert Vertiv GXT5
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #52 background imageLoading...
Page #52 background image
Installation44
2.8.1. First-time Start-up of a Parallel System
IMPORTANT
Do not start the UPS until after the installation is nished, the system is commissioned by an authorized
engineer, and the external input circuit breakers are closed.
CAUTION
Starting the UPS applies mains/utility power to the output terminals. Make sure that the load power is safe and ready to
accept power. If the load is not ready, isolate the load with the output terminal.
The “Parallel” parameters for each UPS in the system must be set and synchronized at rst start-up.
To start and set parameters for the parallel system:
1. Make sure that the output CBs of all units in the parallel system are open (o), then close (turn on) the input
CB on each UPS. Each UPS powers on, a self-check screen displays, and the alarm/run indicators are lit for
about 5 seconds.
2. Wait about 30 seconds to allow the rectier start-up to nish, then at each UPS, set the parallel parameters
as follows:
If the “System parallel settings async” Alarm displays, clear it and proceed. Communication should not
fail after the parallel settings are synchronized
On the display, press Enter to display the Main Menu, then use the arrow buttons to select Settings, and
press Enter.
To adjust the settings, you must enter a password. See Editing Display and Operation Settings on
page 77, for details on entering the password and editing the setting parameters.
Use the arrow buttons to select the Parallel tab, then press Enter to display the parameters list.
Select and Enter each parameter setting, and then use last item in the list, Sync parallel parameters, to
validate the settings. For a full description of UPS display functions and settings, see Operation and Display
Panel on page 53.
After conrming the parallel parameters and each UPS is operating normally, commission the parallel system,
see Commissioning Parallel System below.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Liebert Vertiv GXT5 and is the answer not in the manual?

Liebert Vertiv GXT5 Specifications

General IconGeneral
Output Voltage230V
TopologyDouble Conversion Online
Frequency50/60 Hz
Operating Temperature0°C to 40°C
DimensionsVaries by model
WeightVaries by model
Form FactorRack/Tower
Battery TypeValve Regulated Lead Acid (VRLA)
Communication PortsUSB, RS-232
EfficiencyUp to 95%
Typical Recharge Time3 hours to 90%
Storage Temperature-15°C to 40°C
Humidity0% to 95% non-condensing

Related product manuals