Vertiv | Liebert® GXT5™ | Installer/User Guide 117
Table 7-9 External Battery Cabinet Specifications, 5-kVA to 20-kVA models
MODEL NUMBER GXT5-EBC192VRT3U GXT5-EBC384VRT6U
USED W/UPS MODEL 5 to 10 KVA MODELS 16 to 20 KVA MODELS
Dimensions, D×W×H, in. (mm)
Unit (with bezel) 430 x 630 x 130 (16.9 x 24.8 x 5.1) 430 x 630 x 261 (16.9 x 24.8 x 10.3)
Shipping 800 x 600 x 440 (31.5 x 23.6 x 15.7) 800 x 600 x 580 (31.5 x 23.6 x 22.8)
Weight, kg (lb
)
Unit 57.6 (127) 112 (246.9)
Shipping 80 (176.4) 136 (299.8)
Battery
Type Valve-regulated, non-spillable, lead acid
Qty × Voltage 16 x 12V 32 x 12V
Battery Mfr./Part# 9AH; LEOCH/DJW12-9.0
Backup time See appropriate table for model size in Battery Run Times on page 118.
Environmental Requirements
Operating Temperature, °F (°C) 0 to 40 (32 to 104)
Storage Temperature, °F (°C) -15 to 40 (5 to 104)
Relative Humidity 0 – 95% non-condensing
Operating Elevation Up to 3,000 m (9,842.5 ft.) at 25°C (77°F)
Agency
Safety
UL-1778 (Fifth Edition), C-UL listed, IEC 62040-1: 2008 (First Edition) + Am 1:2013,
EN 62040-1:2008+A1:2013
Transportation
ISTA Procedure 1E

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Liebert Vertiv GXT5 and is the answer not in the manual?

Liebert Vertiv GXT5 Specifications

General IconGeneral
Output Voltage230V
TopologyDouble Conversion Online
Frequency50/60 Hz
Operating Temperature0°C to 40°C
DimensionsVaries by model
WeightVaries by model
Form FactorRack/Tower
Battery TypeValve Regulated Lead Acid (VRLA)
Communication PortsUSB, RS-232
EfficiencyUp to 95%
Typical Recharge Time3 hours to 90%
Storage Temperature-15°C to 40°C
Humidity0% to 95% non-condensing