EasyManuals Logo

Liebert Vertiv GXT5 User Manual

Liebert Vertiv GXT5
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #124 background imageLoading...
Page #124 background image
Specications116
Table 7-8 External Battery Cabinet Specifications, 750 VA to 3000 VA models
MODEL NUMBER GXT5-EBC36VRT2U GXT5-EBC48VRT2U GXT5-EBC72VRT2U
USED W/UPS MODEL 750 to 1,000 VA MODELS 1,500 to 2,000 VA MODELS 3,000 VA MODELS
Dimensions, D×W×H, in. (mm)
Unit (with bezel)
15.7 x 16.9 x 3.4
(400 x 430 x 85)
18.5 x 16.9 x 3.4
(470 x 430 x 85)
21.3 x 16.9 x 3.4
(540 x 430 x 85)
Shipping
24.3 x 22.4 x 10.3
(617 x 570 x 262)
28.2 x 22.4 x 10.3
(717 x 570 x 262)
Weight, kg (lb)
Unit
22.6 (49.72) 28.8 (63.36)
41.2 (90.64)
Shipping
28.7 (63.14) 35 (77)
47.6 (104.72)
Battery
Type Valve-regulated, non-spillable, lead acid
Qty x V x Rating 2 × 3 × 12V × 9.0 Ah 2 × 4 × 12V × 9.0 Ah 2 × 6 × 12V × 9.0 Ah
Battery Mfr./Part# LEOCH/DJW12-9.0
Backup time See Battery Run Times on page 118
Environmental Requirements
Operating Temperature, °F
(°C)
32 to 104 (0 to 40)
Storage Temperature, °F
(°C)
5 to 122 (–15 to 50) High ambient temperatures will reduce battery life
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft (3,000 m) at 104 °F (40 °C)
Agency
Safety
UL-1778 (Fifth Edition), C-UL listed, IEC 62040-1: 2008 (First Edition) + Am 1:2013,
EN 62040-1:2008+A1:2013
EMC
EN 62040-2:2006
EN 61000-3-2:2014
EN 61000-3-3:2013
Transportation ISTA Procedure 1A
Surge Immunity ANSI C62.41 Category B
RFI/EMI CISPR22 Class A (RFI)/ FCC Part 15 (Class A)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Liebert Vertiv GXT5 and is the answer not in the manual?

Liebert Vertiv GXT5 Specifications

General IconGeneral
Output Voltage230V
TopologyDouble Conversion Online
Frequency50/60 Hz
Operating Temperature0°C to 40°C
DimensionsVaries by model
WeightVaries by model
Form FactorRack/Tower
Battery TypeValve Regulated Lead Acid (VRLA)
Communication PortsUSB, RS-232
EfficiencyUp to 95%
Typical Recharge Time3 hours to 90%
Storage Temperature-15°C to 40°C
Humidity0% to 95% non-condensing

Related product manuals