Page 54 of 96
© 2020 LINAK A/S
Only for Non-critical Parallel systems
• The Non-critical Parallel system offers auto-detection for every single power up if a new actuator is added to
the line (system)
• To add or remove actuators from the system, the system needs to be shut down and powered up again.
Please be aware, that after re-powering, the system will not detect if an actuator is missing!
• If adding a new actuator to the system, be aware that the actuator needs to have the same configuration
(Non-critical Parallel) as the existing ones; this can be done via the Buslink software tool
System Monitoring for Parallel
If one of the actuators have one of the following error conditions, the actuator will
immediately STOP:
• H-Bridge fault
• Out of the temperature range (High duty cycle protection)
• Overcurrent (Current cut-off if one or all actuators go in mechanical block)
• SMPS fault
• EOS fault switch
• Hall sensor failure
• Position lost
• Overvoltage (43V DC)
If the actuators are not in parallel when starting up, the next movement will run in the following manner:
Alignment of the parallel actuator system
Start position
Running outwards
When completely aligned, the
parallel run continues outwards
Start position
Running inwards
When completely aligned, the
parallel run continues inwards