Lucent Technologies Galaxy Power System 4848/100
Issue 5 June 2000 Troubleshooting SCF Systems 13 - 5
BATT MIN Battery Thermal
Minor
Alarm on 210A
or 210E unit, if
equipped
Batteries have
exceeded
temperature
threshold.
Call your local RTAC
representative.
BATT MIN Open String Alarm LED on
battery fuse
panel is lit.
Battery fuse has
operated or bat
string switch has
opened.
Replace the operated fuse.
BATT MIN Low Reserve
Time
-- Controller has
calculated that
reserve time is
below alarm
threshold level.
Call your local RTAC
representative.
Table 13-B: Battery Alarms
(See Figure 12-7)
Controller
LED
Controller
Alarm
Status
SCF Controller
Display
Other
Indication(s)
Possible
Problem(s)
Possible Solution(s)