EasyManuals Logo

Lucent Technologies Galaxy 4848/100 User Manual

Lucent Technologies Galaxy 4848/100
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #123 background imageLoading...
Page #123 background image
Lucent Technologies Galaxy Power System 4848/100
Issue 5 June 2000 Troubleshooting Millennium Systems 14 - 3
AC Alarm LED
Table 14-A: AC Alarms
(See Figure 12-8)
Controller
LED
Controller
Alarm
Status
Millennium
Controller Display
Other
Indication(s)
Possible Problem(s) Possible Solution(s)
AC MIN AC Fail ACF on
rectifier
display
Rectifier is not
receiving ac power:
•AC input circuit
breaker has
operated.
•AC input voltage is
out of range.
•Internal rectifier
failure
1. Verify that ac circuit
breaker is closed; close
circuit breaker if
operated.
2. If the problem is not
corrected, replace the
rectifier.
AC MIN Engine Transfer
Timeout
Engine may
have alarm.
Remote engine or
connection to
engine has failed.
Call your local RTAC
representative.
AC MIN Phase Alarm PF on
rectifier
display
Phase failure:
•Rectifier high
voltage shutdown
•External phase
imbalance or
failure
•Internal rectifier
failure
1. Toggle the ON/STBY
switch into the STBY
position and then back
into the ON position.
2. If the problem is not
corrected, replace the
rectifier.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lucent Technologies Galaxy 4848/100 and is the answer not in the manual?

Lucent Technologies Galaxy 4848/100 Specifications

General IconGeneral
BrandLucent Technologies
ModelGalaxy 4848/100
CategoryPower Supply
LanguageEnglish

Related product manuals