Lucent Technologies Galaxy Power System 4848/100
Issue 5 June 2000 Troubleshooting Millennium Systems 14 - 15
BD and RM Alarm
LEDs, or No LED
Table 14-F: Miscellaneous Alarms
Controller
LED
Controller
Alarm
Status
Millennium
Controller Display
Other
Indication(s)
Possible Problem(s) Possible Solution(s)
BD MAJ Battery on
Discharge
Rectifiers
may say
ACF.
Temporary
condition that may
be associated with
other alarms
Call your local RTAC
representative.
RM MIN Module Failure Green LED
on RPM will
not blink.
Remote Peripheral
Module has failed.
Call your local RTAC
representative.
RM MIN Measurement Out
of Range
-- •Data being sensed
exceeds remote
peripheral
module’s
capability.
•Remote peripheral
module has failed.
Call your local RTAC
representative.
None MAJ Auxiliary Major Auxiliary
equipment
may have
alarm.
Problem with
operation of
auxiliary equipment
Call your local RTAC
representative.
None MIN Auxiliary Minor Auxiliary
equipment
may have
alarm.
Problem with
operation of
auxiliary equipment
Call your local RTAC
representative.
None None None •STBY LED
on rectifier
is lit.
•TR on
rectifier
display
Remote transfer:
•Rectifier is in
STBY.
Remove the remote
standby command issued
by the controller.
None None None Red LED is
lit on some
battery
contactor
drive
boards,
while green
LED is lit on
others.
If a green LED is lit
despite a contactor
open command
issued by the
controller, the drive
card or the
contactor has failed.
Call your local RTAC