Lucent Technologies Galaxy Power System 4848/100
Issue 5 June 2000 Troubleshooting Millennium Systems 14 - 11
RECT Alarm LED
Table 14-E: Rectifier Related Alarms
(See Figures 12-6 and 12-8)
Controller
LED
Controller
Alarm
Status
Millennium
Controller Display
Rectifier
LED
Rectifier
Display
Possible
Problem(s)
Possible Solution(s)
RECT MAJ ID Not Configured None None Rectifier ID
number has not
been set.
1. Press ON/STBY
switch up and hold
for five seconds
until display starts
blinking “0”.
2. Release switch;
display should
continue to blink.
3. Depress switch and
release. Display
will increment up
one number on each
release of the
switch, but will
remain flashing.
4. Once the desired ID
number appears,
depress and hold the
switch for five
seconds. The
display will cease to
blink, and then
revert to the
rectifier current.
RECT MAJ ID Conflict None None Two or more
rectifiers have
the same ID
number.
See above.
RECT MAJ Multiple Rectifier
Fail
ALM None More than one
rectifier has an
ALM LED lit.
See alarms listed
below.
RECT MAJ High Voltage
Alarm
ALM HO •Lightning has
struck system.
•Internal rectifier
failure
1. Toggle the ON/
STBY switch into
the STBY position
and then back into
the ON position.
2. If the problem is not
corrected, replace
the rectifier.