Lucent Technologies Galaxy Power System 4848/100
14 - 12 Troubleshooting Millennium Systems Issue 5 June 2000
RECT MIN Rectifier Fail ALM HO High output
voltage:
•Rectifier high
voltage
shutdown
•Internal rectifier
failure
1. Verify the
configurable HV
thresholds in the
controller.
2. Toggle the ON/
STBY switch into
the STBY position
and then back into
the ON position.
3. If the problem is not
corrected, replace
the rectifier.
RECT MIN Rectifier Fail ALM TA Thermal alarm:
•Excessive
ambient
temperature
•Internal rectifier
failure
1. Verify that there is
no obstruction of
the fan inlet.
2. Toggle the ON/
STBY switch into
the STBY position
and then back into
the ON position.
3. If the problem is not
corrected, replace
the rectifier.
RECT MIN Rectifier Fail ALM CB Circuit breaker
alarm:
•DC output
circuit breaker
open
•Internal rectifier
failure
1. Toggle the ON/
STBY switch into
the STBY position;
toggle the DC
output circuit
breaker into the
OFF position and
then into the ON
position. Return the
ON/STBY switch to
the ON position.
2. If the problem is not
corrected, replace
the rectifier.
Table 14-E: Rectifier Related Alarms
(See Figures 12-6 and 12-8)
Controller
LED
Controller
Alarm
Status
Millennium
Controller Display
Rectifier
LED
Rectifier
Display
Possible
Problem(s)
Possible Solution(s)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lucent Technologies Galaxy 4848/100 and is the answer not in the manual?

Lucent Technologies Galaxy 4848/100 Specifications

General IconGeneral
BrandLucent Technologies
ModelGalaxy 4848/100
CategoryPower Supply
LanguageEnglish

Related product manuals