Lucent Technologies Galaxy Power System 4848/100
Issue 5 June 2000 Troubleshooting SCF Systems 13 - 17
RECT MIN High Float
Voltage
None None Configuration
problem
Call your local RTAC
representative.
RECT MIN Excess
Rectifier Drain
None None Internal rectifier
fault
Replace rectifier.
RECT MIN Excess System
Drain
None None System load
exceeds shunt
rating.
Call your local RTAC
representative.
RECT MIN Limited
Recharge
None None Rectifier capacity
has been exceeded.
Install more rectifiers.
RECT MIN External
Transfer
Shutdown
STBY TR System is
operating on
external engine.
No action required.
RECT MIN Rectifier Fail ALM FSE Fuse alarm:
•DC fuse open
•Internal rectifier
failure
1. Toggle the ON/STBY
switch into the STBY
position and then back
into the ON position.
2. If the problem is not
corrected, replace the
rectifier.
Table 13-E: Rectifier Related Alarms
(See Figures 12-6 and 12-8)
Controller
LED
Controller
Alarm
Status
SCF
Controller
Display
Rectifier
LED
Rectifier
Display
Possible
Problem(s)
Possible Solution(s)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lucent Technologies Galaxy 4848/100 and is the answer not in the manual?

Lucent Technologies Galaxy 4848/100 Specifications

General IconGeneral
BrandLucent Technologies
ModelGalaxy 4848/100
CategoryPower Supply
LanguageEnglish

Related product manuals