M
AVTM246004 BITE 2/2P Rev 4 July 2011
47
5
MODIFIED PROCEDURES FOR SPECIAL
CONDITIONS
Overview
This chapter explains how to perform alternative test
procedures, including reversing the current source leads
and sectioning battery systems to correct high or low current
situations.
This chapter also describes optional equipment that can be
used with the BITE 2 and BITE 2P test instruments.
Reversing the Current Source Leads
If the transmitter displays a high or low current message,
you need to modify the test procedure. See the following
subsections for alternative test procedures.
Figure 5-1 shows a battery system with a single string of
cells. If a high or low current message is displayed on the
receiver after you connect the current source leads to a
similar battery configuration, try reversing the polarity of the
current source leads. Doing so shifts the test current by 180
degrees and offsets the effect of the system ripple current in
the receiver. This helps ensure sufficient test current in the
section of the battery string to enable computation of cell
impedance or strap resistance.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Megger BITE 2 and is the answer not in the manual?

Megger BITE 2 Specifications

General IconGeneral
BrandMegger
ModelBITE 2
CategoryTest Equipment
LanguageEnglish

Related product manuals