M
AVTM246004 BITE 2/2P Rev 4 July 2011
48
J2
From transmitter
(current source
leads)
Figure 5-1: Reversing the current source leads on a single string of cells
when a high or low current message is displayed.
Verifying the Source Current
A low current indication on the transmitter’s analog or
digital meter can be caused by high resistance in the cell
string. To verify whether the magnitude of the source current
is within the required limits (3-15 A):
This temporarily “disconnects”
the transmitter and blocks the
current from going to the
battery.
1. Press the Current switch on the BITE 2/2P transmitter
to the ( (OFF) position.
2. Disconnect the current source leads from the battery.
3. Connect the current source lead clips together and
restart current flow by pressing the BITE 2/2P
transmitter Current On/Off switch to the (ON) position.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com