EasyManuals Logo

Megger BITE 2 User Manual

Megger BITE 2
135 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #92 background imageLoading...
Page #92 background image
M
AVTM246004 BITE 2/2P Rev 4 July 2011
91
A
APPENDIX A: TECHNICAL SPECIFICATIONS
Application
The BITE 2/2P can test lead-acid and nickel-cadmium
cells of less than 7000 Ah capacity.
Tests on most battery systems require the standard
clamp-on current sensor (CT) with a 2-inch opening.
Maximum total voltage at BITE2/2P transmitter current
source connections is 275 V dc (larger battery systems
can be sectioned to accommodate this specification).
Electrical
BITE 2 and BITE 2P
Transmitters
Supply Voltage:
IEC 1010-1 Class I, Installation category II
Cat Nos. 246002 & 246004: 100 to 240 V nominal,
(50/60 Hz). Do NOT exceed 264 V max.
Source Output Current:
IEC 1010-I Installation category I
10 A nominal, 50/60 Hz operation
Output:
6.50 V dc @ 1.10 A dc charging (max)
9.60 V dc open circuit
Maximum Battery Test Voltage:
275 V dc at transmitter source lead terminals
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Megger BITE 2 and is the answer not in the manual?

Megger BITE 2 Specifications

General IconGeneral
BrandMegger
ModelBITE 2
CategoryTest Equipment
LanguageEnglish

Related product manuals