Recording data 4.1 Trend file
EM-7361 P53
MG CO., LTD.
www.mgco.jp
Time correction
If the PC time is corrected during trend data recording, the time is corrected at regular intervals for a fixed
period of time to ensure time continuity. During the time correction process, the time on the WEB display is
showed in yellow. -> 5.1 Description of
Range of correction
Process
Within -180 to 0 sec.
The recording cycle is extended until the corrected current time catches up with the time
in the process of trend data recording. After catching up, the recording cycle is restored.
Within 0 to 180 sec.
Complements data for missing recording cycles. In addition, the recording cycle is
shortened until the time in the process of trend data recording catches up with the
corrected current time. After catching up, the recording cycle is restored.
Other than those above
The time change is applied immediately and is not equalized.
If time is corrected again during the equalization process, it works as follows:
If the change reduces the difference between the current time after the correction and the
current time before the correction, the equalization process continues.
Otherwise, the change is applied immediately.