Meter Operations 3.4.4
otherwise, touch the BACK (F1) button to
return to the CURRENT sub-menu.
TouCH BuTTon funCTions:
to increase the number, touch the UP (F2)
button.
to decrease the number, touch the DOWN
(F3) button.
In the input mode, the UP (F2) and DOWN (F3)
buttons will become active and the background
colour of the active eld will be changed to white.
Demand interval can be set from 60 secs to 1800
secs in steps of 60 secs whereas the number of
sub interval blocks can be set from 2 to 120.
noTE:
The demand interval in secs must be whole
number multiples of the number of sub
intervals and the sub interval period must be
longer than 15 secs.
to select the next eld to change, touch the
NEXT (F4) button and repeat the above 2
steps.
to save the settings and/or return to the
Current Demand page, touch the BACK
(F1) button.
TouCH BuTTon funCTions:
to abort saving the settings and return to the
Current Demand page, touch the NO (F3)
button.
otherwise, touch the YES (F2) button to save
the settings and the user will be prompted for
password authentication as per section 3.2
The user will be prompted to conrm the saving
of settings.
noTE:
When the Demand Interval is changed, the
sub intervals defaults to 2. This can however,
be changed separately when the NEXT (F4)
button is touched.