9. Fieldbus interface | 9.2 - Scale protocol | 109
9.2.1 Data exchange range
Overview
Byte 0, 1, 2, 3 4 5 6, 7
MOSI Write data Read_Value_Select Write_Value_Select Control bits
MISO Read data Read_Value_Selected Status bits Status bits
Write window (MOSI)
Byte Field Description
0 Write data (MSB)
1 Write data
2 Write data
3 Write data (LSB)
Contains the data to be
written, e.g., analog output.
4 Read_Value_Select Selects the function for
reading data.
5 Write_Value_Select Selects the function for
writing data.
6 free free free free free free free free
7 Get Fix
Tare
Set Fix
Tare
Res
Pow
er
Res
Test
Set
Test
Res
Tare
Set
Tare
Set
Zero
In direct access, control
bits are independent of the
write or read request.
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Field Size Function
Write data 4 bytes Data to be written as a binary 32-bit value with
plus or minus sign.
Data type: DINT
Read_Value_Select 1 byte Function for selecting the read request
Write_Value_Select 1 byte Function for selecting the write request
ResPower 1 bit PowerFail is reset.
ResTest 1 bit The test operating mode is finished.
SetTest 1 bit The test operating mode is started.