EasyManuals Logo

Mitsubishi FX-20P-E User Manual

Mitsubishi FX-20P-E
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #117 background imageLoading...
Page #117 background image
FX-20P-E Handy programming panel Message List 11
11-5
LADDER ERR
6607 1) Illegal FOR and NEXT designation
Nesting level deeper than 5 levels
2) One of the following commands is designated in the FOR-NEXT loop.
STL, RET, MC, MCR, IRET, SRET, FEND, END
6608 1) Illegal MC and MCR designation
2) No MCR N0
3) One of the following commands is designated in the MC-MCR loop.
SRET, IRET, I (interrupt)
6609 Other
RUNTIME ERROR *
6701 No jump destination of CJ or CALL. A label follows after the END
instruction. An independent label is in the FOR-NEXT loop or a
subroutine program.
6702 CALL nesting level deeper than 5 levels
6703 Interrupt nesting level deeper than 2 levels
6704 FOR-NEXT loop nesting level deeper than 5 levels
6705 A device other than a valid is used for an applied instruction operand.
6706 The device number or data designated as an applied instruction operand
is outside the allowable designation range.
6707
File register operation is accessed without allocating the file register area.
6708 FROM/TO instruction error.
6709 Other (No IRET or SRET or illegal FOR-NEXT loop)
Error message Error code Description