7 Description of Function Codes NICE7000 User Manual
- 142 -
process (deceleration process) of the S curve.
F3-03 (F3-07) is the time for the rate to increase from 0 to the value set in F3-02 (F3-05) in
the end jerk segment of the S curve. The larger the value is, the smoother the jerk is.
F3-04 (F3-06) is the time for the rate to decrease from the value set in F3-02 (F3-05) to 0 in
the start jerk segment of the S curve. The larger the value is, the smoother the jerk is.
Figure 7-2 Setting the running curve
t (time)
V (speed)
F3-04
F3-02
F3-03
F3-09
F3-07
F3-05
F3-06
F2-22
F3-00
F3-01
Function Code Parameter Name Setting Range Default Unit Property
F3-08
Special deceleration rate 0.800–1.500
0.900 m/s2
It is used to set the deceleration rate in elevator slow-down, inspection, and shaft auto-
tuning.
This parameter is not used during normal running. It is used only when the elevator position
is abnormal or the slow-down signal is abnormal, preventing over travel top terminal or over
travel bottom terminal.
Function Code Parameter Name Setting Range Default Unit Property
F3-09
Pre-deceleration distance 0–50.0
0.0 mm
It is used to set the pre-deceleration distance of the elevator in distance control, as shown in
Figure 7-2.
Function Code Parameter Name Setting Range Default Unit Property
F3-10 Re-leveling speed 0.040–0.080 0.040 m/s
It is used to set the elevator speed during re-leveling.
This parameter is valid only when the pre-open module (MCTC-SCB-A) is added to
implement the re-leveling function (set in F6-09 Bit2 = 1).
Function Code Parameter Name Setting Range Default Unit Property
F3-11
Inspection speed 0.080–0.630
0.250 m/s