9.3.2 Installation of AC Input Reactor on Power Input Side
An AC input reactor is installed to eliminate the harmonics of the input current. As an optional
device, the reactor can be installed externally to meet strict requirements of an application
environment for harmonics. The following table lists the recommended manufacturers and
models of input reactors.
Table 9-2 Recommended manufacturers and models of AC input reactors
Controller Model
Power Capacity
(kVA)
Rated Input
Current (A)
AC Input Reactor Model
(Inovance)
Three-phase 380 V
NICE-LQX-4002-A/B/C0
4.0 6.5 MD-ACL-7-4T-222-2%
NICE-LQX-4003-A/B/C0
5.9 10.5 MD-ACL-10-4T-372-2%
NICE-LQX-4005-A/B/C0
8.9 14.8 MD-ACL-15-4T-552-2%
NICE-LQX-4007-A/B/C0
11.0 20.5 MD-ACL-30-4T-113-2%
NICE-LQX-4011-A/B/C0
17.0 29.0 MD-ACL-30-4T-113-2%
NICE-LQX-4015-A/B/C0
21.0 36.0 MD-ACL-40-4T-153-2%
NICE-LQX-4018-A/B/C0
24.0 41.0 MD-ACL-50-4T-183-2%
NICE-LQX-4022-A/B/C0
30.0 49.5 MD-ACL-50-4T-183-2%
NICE-LQX-4030-A/B/C0
40.0 62.0 MD-ACL-80-4T-303-2%
NICE-LQX-4037-A/B/C0
57.0 77.0 MD-ACL-80-4T-303-2%
NICE-LQX-4045-A/B/C0
69.0 93.0 MD-ACL-120-4T-453-2%
NICE-LQX-4055-A/B/C0
85.0 113.0 MD-ACL-120-4T-453-2%
Three-phase 220 V
NICE-LQX-2002-A/B/C0
4.0 11.0 MD-ACL-15-4T-222-2%
NICE-LQX-2003-A/B/C0
5.9 17.0 MD-ACL-30-4T-222-2%
220-NICE-LQX-4007-A/B/C0
17.0 29.0 MD-ACL-30-4T-113-2%
220-NICE-LQX-4011-A/B/C0
21.0 36.0 MD-ACL-50-4T-113-2%
220-NICE-LQX-4015-A/B/C0
24.0 41.0 MD-ACL-50-4T-153-2%
220-NICE-LQX-4018-A/B/C0
30.0 40.0 MD-ACL-50-4T-183-2%
220-NICE-LQX-4022-A/B/C0
40.0 49.0 MD-ACL-50-4T-183-2%
220-NICE-LQX-4030-A/B/C0
57.0 61.0 MD-ACL-80-4T-303-2%
Single-phase 220 V
NICE-LQX-2002-A/B/C0
2.3 13.2 Consult the manufacturer.
NICE-LQX-2003-A/B/C0
3.4 17.0 Consult the manufacturer.
220-NICE-LQX-4007-A/B/C0
9.8 29.0 Consult the manufacturer.
220-NICE-LQX-4011-A/B/C0
12.1 36.0 Consult the manufacturer.