2) Group control
•
Parameter setting
To use group control, connect the CAN2+ and CAN2- terminals of CN6 on the controllers for
group control.
The following table lists the parameter setting of group control.
Table 5-8 Parameter setting of group control
Function Code
Parameter Name
Setting Range
Setting in Group Control
Fd-00
Number of elevators in
parallel/group mode
3–8
3–8
Fd-01
Elevator No.
1–8
1: master elevator
2–8: slave elevator
Fd-02
Parallel/Group control mode
0–2
2
•
Address Setting of Physical Floors
The setting principle is the same as that for parallel control.
Assume that there are two elevators in parallel mode. Elevator 1 stops at oor B1, oor
1, oor 2, and oor 3; elevator 2 stops at oor 1, oor 3, and oor 4; elevator 3 stops at
oor B1, oor 1, oor 2, and oor 3. Now, set related parameters and HCB addresses