This function is used only in the heavy-load test. Once the test is complete, prohibit overload
running immediately.
Function Code Parameter Name Setting Range Default Unit Property
F7-07
Limit switch
0: Enabled
1: Disabled
0 - ☆
It is used to enable the limit switch function.
The limit switch is disabled only in the test of the nal limit switch. Use the function with caution.
Function Code Parameter Name Setting Range Default Unit Property
F7-08 Time interval of random running 0–1000 0 s ☆
It is used to set the time interval between two times of random running.
Function
Code
Parameter Name Setting Range Default Unit Property
F7-09
Accumulative energy consumption 0–65535
0 kW ●
F7-10
Accumulative feedback energy 0–65535
0 kW ●
These parameters record the energy consumed during elevator running and the feedback
energy from the energy feedback unit.
Function Code Parameter Name Setting Range Default Unit Property
F7-26
Commissioning
function selection
0: No operation
1: Shaft auto-tuning
0 - ★
It is used to set whether to perform shaft auto-tuning.
Group F8: Auxiliary Logic Parameters
Function Code Parameter Name Setting Range Default Unit Property
F8-00
Load for load cell auto-tuning 0–100
0 % ★
It is used to set the load for load cell auto-tuning.
To perform load cell auto-tuning, do as follows:
1. Ensure that F2-11 is set to 0 and F5-36 is set to 2 or 3 to make the system allow load
cell auto tuning.