- 97 -
call communication of door 1 is executed by Mod1 and that of door 2 is executed by Mod2.
The NICE7000 supports opposite door control on a maximum of 56 oors.
The following table describes the control modes and related parameter setting.
Table 5-10 Opposite door control modes and parameter setting
Opposite Door Control
Mode
Parameter Setting Function Description
Mode 1
Simultaneous
control
Fb-00 = 2
Fb-01 = 0
The front door and back door acts
simultaneously upon arrival for hall calls and
car calls.
Mode 2
Hall call
independent,
car call
simultaneous
Fb-00 = 2
Fb-01 = 5 (Bit0, Bit2 =
1)
The corresponding door opens upon arrival
for hall calls from this door.
The front door and back door act
simultaneously upon arrival for car calls.
Mode 3
Hall call
independent,
car call
manual
control
Fb-00 = 2
Fb-01 = 325 (Bit0, Bit2,
Bit6, Bit8 = 1)
The corresponding door opens upon arrival
for halls call from this door.
Upon arrival for car calls, the door to open
is selected between the front door and back
door by using the door switchover switch.
Note: The switchover switch can be
connected to the HCB-B inside the car or
MCB (function 42/142: Back door selection).
Mode 4
Hall call
independent,
car call
independent
Fb-00 = 2
Fb-01 = 271 (Bit 0, Bit1,
Bit2, Bit3, Bit8 = 1)
The corresponding door opens upon arrival
for halls call and car calls from this door.
In the re emergency, inspection, and re-leveling state, the opposite door is under simultaneous
control rather than independent control.