NICE7000 User Manual 7 Description of Function Codes
- 153 -
section 5.5.1.
13: Emergency evacuation automatic switchover
When detecting that the bus voltage declines to a certain value after power failure occurs on
the mains supply, the controller outputs this signal and uses the EPS for temporary power
supply, implementing emergency evacuation running.
Only Y6 can be allocated with this function because the controller needs to depend on its
residual power to drive the relay at power failure of the mains supply.
14: Controller healthy
The terminal with the function has output when the controller operates properly.
15: Emergency buzzer control
The terminal with the function has output when the system is in the emergency evacuation
running state. The buzzer tweets to prompt.
16: Higher-voltage startup of brake
This function is used for the brake that keeps the release state with voltage reduction. The
terminal with this function keeps the output for a certain time to release the brake, and then
the voltage is reduced to keep the brake release state.
17: Elevator running in up direction
The terminal with the function has output when the elevator runs in the up direction.
18: Lamp/Fan running
It is used for the lamp/fan running output, the same as the energy saving control output of
the CTB.
19: Medical sterilization
It is used to control the output of the ultraviolet sterilizing lamp signal. After the elevator
stops running and the lamp/fan stops operating, the medical sterilization output is started.
20: Non-door zone stop
The terminal with this function has output when the elevator stops at the non-door zone.
21: Electric lock
It is used to control applying and releasing of the electric lock in the case of manual door.
22: Non-service state
It is output when the elevator is in the non-service state and cannot respond to hall calls.
Group F6: Elevator Logic Parameters
Function Code Parameter Name Setting Range Default Unit Property
F6-00
Top oor of the elevator F6-01 to 56
9 -
F6-01
Bottom oor of the elevator 1 to F6-00
1 -
These two parameters are used to set the top floor and bottom floor of the elevator,