EasyManua.ls Logo

Monarch NICE7000 - Group FA: Auxiliary Parameters

Monarch NICE7000
237 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NICE7000 User Manual 7 Description of Function Codes
- 175 -
In normal running state, if the continuous motor running time in the same direction between
two adjacent oors exceeds the setting of this parameter but no leveling signal is received,
the system will perform protection.
This parameter is mainly used for over-time protection in the case of steel rope slipping on
the traction sheave.
If this parameter is set to a value smaller than 3s, it becomes invalid.
Function Code Parameter Name Setting Range Default Unit Property
F9-03
Accumulative working hours 0–65535
0 h
F9-04
Accumulative running hours 0–65535
0 h
F9-05
Accumulative working days 0–65535
0 day
These parameters record the accumulative running and working time.
The working time counts the time since use, regardless of running or stop.
The running time counts only the elevator running time.
Function Code Parameter Name Setting Range Default Unit Property
F9-06
High byte of running times 0–9999
0 -
F9-07
Low byte or running times 0–9999
0 -
Running times of the elevator = F9-06 x 10000 + F9-07.
Function Code Parameter Name Setting Range Default Unit Property
F9-12
Clock: year 2000–2100
2010 YYYY
F9-13
Clock: month and day 1.01–12.31
301 MM.DD
F9-14
Clock: hour and minute 0–23.59
0 HH.MM
These parameters are used to set the current date and time of the system.
Group FA: Auxiliary Parameters
Function Code Parameter Name Setting Range Default Unit Property
FA-00
Group FA security password 0–65535
01000 -
You are allowed to view and modify group FA parameters only after entering the security
password.
Function Code Parameter Name Setting Range Default Unit Property
FA-01
Display in running state 1–65535
65535 -
It is used to set the running parameters displayed on the operation panel when the elevator
is in the running state.
FA-01 includes 16 binary bits, each dening a parameter. A total of 16 parameters can be
can be displayed during running.

Table of Contents

Related product manuals