- 94 -
In parallel mode, the physical floor numbers of the same floor for two elevators are
consistent.
If the oor structures of two elevators are different, physical oors should start with the
oor with the lowest position.
The physical oors at the overlapped area of the two elevators are the same.
Even if one elevator does not stop a oor in the overlapped area, a leveling plate should
be installed there. You can make the elevator not stop at the oor by setting service
oors.
When two elevators are in parallel mode, the addresses of the HCBs should be set
according to physical oors. Parallel running can be implemented only when the HCB
address set for one elevator is the same as that for the other elevator in terms of the
same oor.
In parallel mode, the top oor (F6-00) and bottom oor (F6-01) of the elevators should be set
based on corresponding physical oors.
Assume that there are two elevators in parallel mode. Elevator 1 stops at oor B1, oor 1,
oor 2, and oor 3, while elevator 2 stops at oor 1, oor 3, and oor 4. Now, you need to
set related parameters and HCB addresses according to the following table.
Table 5-7 Parameter setting example of parallel control
Elevator 1 Elevator 2
Number of elevators in
parallel/group mode (Fd-00)
2 2
Elevator No. (Fd-01)
1 2
Actual oor Physical oor
HCB
address
HCB display HCB address HCB display
B1 1 1 FE-01 = 1101 / /
1 2 2 FE-02 = 1901 2 FE-02 = 1901
2 3 3 FE-03 = 1902
Non-stop oor
but leveling plate
required
FE-03 = 1902
3 4 4 FE-04 = 1903 4 FE-04 = 1903
4 5 / / 5 FE-05 = 1904
Bottom oor (F6-01)
1 2
Top oor (F6-00)
4 5
Service oor (F6-05)
65535 65531 (not stop at physical oor 3)