5 System Commissioning and Functions NICE7000 User Manual
- 94 -
In parallel mode, the physical floor numbers of the same floor for two elevators are
consistent.
If the oor structures of two elevators are different, physical oors should start with the
oor with the lowest position.
The physical oors at the overlapped area of the two elevators are the same.
Even if one elevator does not stop a oor in the overlapped area, a leveling plate should
be installed there. You can make the elevator not stop at the oor by setting service
oors.
When two elevators are in parallel mode, the addresses of the HCBs should be set
according to physical oors. Parallel running can be implemented only when the HCB
address set for one elevator is the same as that for the other elevator in terms of the
same oor.
In parallel mode, the top oor (F6-00) and bottom oor (F6-01) of the elevators should be set
based on corresponding physical oors.
Assume that there are two elevators in parallel mode. Elevator 1 stops at oor B1, oor 1,
oor 2, and oor 3, while elevator 2 stops at oor 1, oor 3, and oor 4. Now, you need to
set related parameters and HCB addresses according to the following table.
Table 5-7 Parameter setting example of parallel control
Elevator 1 Elevator 2
Number of elevators in
parallel/group mode (Fd-00)
2 2
Elevator No. (Fd-01)
1 2
Actual oor Physical oor
HCB
address
HCB display HCB address HCB display
B1 1 1 FE-01 = 1101 / /
1 2 2 FE-02 = 1901 2 FE-02 = 1901
2 3 3 FE-03 = 1902
Non-stop oor
but leveling plate
required
FE-03 = 1902
3 4 4 FE-04 = 1903 4 FE-04 = 1903
4 5 / / 5 FE-05 = 1904
Bottom oor (F6-01)
1 2
Top oor (F6-00)
4 5
Service oor (F6-05)
65535 65531 (not stop at physical oor 3)