NICE7000 User Manual 4 Use of the Commissioning Tools
- 71 -
Button Function
PRG
Press this button in any state to exit the current operation and enter the function menu
mode (that is, display the current function group number).
UP
Press this button to increase the function group number or data.
In group F6 menu, this button is used to input the door open command.
SET
Enter the function menu edit mode; conrm and save the current operation.
In group F6 menu, this button is used to input the door close command.
The following gure shows the setting of increasing the called oor to 5.
Figure 4-2 Setting the called oor
05
F0
04
(Select the function
code group)
(Set the
parameter value)
Level-I menu
Level-II menu
PRG
Without
saving
SET
Saving
When there is a blinking digit,
press the UP button to modify it.
01
SET
Enter
Current floor
UP
Increase
(default display)
F1
PRG
Switch
UP
Increase
The function code groups displayed on the keypad are described as follows:
1. F0: display of oor and running direction
The F0 menu is displayed on the keypad by default upon power-on. The first LED
indicates the running direction, while the last two LEDs indicate the current oor number
of the elevator.
When the elevator stops, the rst LED has no display. When the elevator runs, the rst
LED blinks to indicate the running direction.
When a system fault occurs, the 7-segment LEDs automatically display the fault code
and blink. If the fault is reset automatically, the F0 menu is displayed.
Running
direction
Current floor
Stop state: no display
RUN state: running direction in blinking
Fault state: fault code in blinking
2. F1: command input of the running oor
After you enter the F1 menu, the 7-segment LEDs display the bottom oor (F6-01). You
can press the UP button to set the destination oor within the range of lowest to top and
then press the SET button to save the setting. The elevator runs to the destination oor,
and the display switches over to the F0 menu at the same time.