determined by the number of actually installed leveling plates.
Function Code Parameter Name Setting Range Default Unit Property
F6-02
Parking oor F6-01 to F6-00
1 - ★
When the idle time of the elevator exceeds the value set in F9-00, the elevator returns to the
parking oor automatically.
Function Code Parameter Name Setting Range Default Unit Property
F6-03
Fire emergency oor F6-01 to F6-00
1 - ★
When entering the state of returning to the re emergency oor, the elevator returns to this
oor.
Function Code Parameter Name Setting Range Default Unit Property
F6-04
Elevator lock oor F6-01 to F6-00
1 - ★
When entering the elevator lock state, the elevator returns to this oor.
Function Code Parameter Name Setting Range Default Unit Property
F6-05 Service oors 1 0–65535 65535 - ★
F6-06 Service oors 2 0–65535 65535 - ★
F6-07 Service oors 3 0–65535 65535 - ★
F6-08 Service oors 4 0–65535 65535 - ★
These parameters are used to set the service oors among oors 1–56.
•
Service oors 1: oors 1–16
•
Service oors 2: oors 17–32
•
Service oors 3: oors 33–48
•
Service oors 4: oors 49–56
Whether service oors of a parameter are allowed is indicated by a 16-bit binary number.
The 16 bits respectively correspond to 16 oors from low to high. If a bit is set to 1, the
elevator will respond to calls of this oor; if this bit is set to 0, the elevator will not respond to
calls of this oor.
The following part takes F6-05 as an example to describe how to set the service oors.
F6-05 is enabled through bit addressing.
The 16 bits of the function code respectively correspond to 16 oors. If a bit is set to 1, the
elevator will respond to calls of this oor; if this bit is set to 0, the elevator will not respond to
calls of this oor.