5 System Commissioning and Functions NICE7000 User Manual
- 98 -
HCB addresses of door 1 and door 2 are set based on the actual physical addresses and
must be consistent.
Figure 5-13 HCB wiring of opposite door control
+24V
COM
Mod1+
+24V
COM
PRG
UP
SET
NICE7000
CN3
CN6
Operation box
of top floor
Operation box
of Nth floor
Operation box
of bottom floor
Front door HCB
Operation box
of top floor
Operation box
of Nth floor
Operation box
of bottom floor
Back door HCB
Mod1-
Mod2+ Mod2-
The car call signals of front door and back door are respectively connected to CN7 and CN8 on
the CTB.
The parameter setting of Fb-01 for opposite door control is described as follows:
Bit Function Setting Bit Function Setting
Bit0
Hall call
button
display
1
Independent for
front door and
back door
Bit1
Car call
button
display
1
Independent for front
door and back door
0
Consistent for front
door and back
door
0
Consistent for front
door and back door
Bit2
Hall call door
open mode
1
Corresponding
door open
Bit3
Car call door
open mode
1
Corresponding door
open
0
Both doors open
0
Both doors open