- 190 -
Function
Code
Parameter
Name
Setting Range Default Unit Property
FL-17
HCB:JP1 input
1: Elevator lock signal
2: Fire emergency signal
3: Current oor forbidden
4: VIP oor signal
5: Security oor signal
6: Service oor switchover
7: Parking oor switchover
8: Down collective selective switch
9: Peak service switch
10: Fire emergency oor switchover
1 - ★
FL-18
HCB:JP2 input
2 - ★
These parameters are used to set the functions of input terminals on the HCB.
Function
Code
Parameter Name Setting Range Default Unit Property
FL-19
HCB:JP1 output
0: Invalid
1: Up arrival indicator
2: Down arrival indicator
3: Fault output
4: Non-door zone stop output
5: Non-service state output
6: Buzzer output
1 - ★
FL-20
HCB:JP2 output
2 - ★
These parameters are used to set the functions of output terminals on the HCB.
The setting is effective to HCBs at all oors.
Group Fr: Leveling Adjustment Parameters
Function Code Parameter Name Setting Range Default Unit Property
Fr-00
Leveling adjustment function
0: Disabled
1: Enabled
0 - ★
This parameter is used to enable the leveling adjustment function.
Function
Code
Parameter Name Setting Range Default Unit Property
Fr-01
Leveling adjustment record 1
00000–60060
30030 mm ★
Fr-02
Leveling adjustment record 2
30030 mm ★
… …
Fr-28
Leveling adjustment record 28
30030 mm ★