7 Description of Function Codes NICE7000 User Manual
- 184 -
Function Code
Parameter Name Setting Range
Default Unit Property
FC-47
11th fault subcode 0–65535
0 -
FC-48
11th fault month and day 0–1231
0 MM.DD
FC-49
11th fault hour and minute 0–2359
0 HH.MM
FC-50
11th fault information 0–65535
0 -
These parameters record the rst 10 faults of the elevator among the last 20 faults.
The fault code is a 4-digit number. The two high digits indicate the oor where the car is
located when the fault occurs, and the two low digits indicate the fault code. For example,
the FC-46 is 0835, indicating that when the 11th fault (Err35) occurs, the car is near oor 8.
The fault subcode is used to locate the causes of the fault. The specific fault time is
recorded in month, day, hour and minute.
Group Fd: Parallel/Group Control Parameters
Function Code Parameter Name Setting Range Default Unit Property
Fd-00
Number of elevators in
parallel/group mode
1–3
1 -
Fd-01
Elevator No. 1–3
1 -
These parameters are used to set the number of elevators and elevator No. in in parallel//
group mode.
The NICE7000 supports parallel control of two elevators or group control of up to eight
elevators.