The parameter setting in such wiring mode is described in the following table.
Table 5-4 Parameter setting under the shorting PMSM stator scheme
Function
Code
Parameter Name Value Description
F5-18
X18 function selection
30
Allocate X18 with "Input of shorting PMSM
stator feedback signal".
F5-34
Y3 function selection
12
Allocate Y3 with "Output of shorting PMSM
stator contactor feedback signal".
F6-10
Elevator function
selection 2
-
Bit8 = 0: NC output contactor
Bit8 = 1: NO output contactor
5.5.2 Parallel/Group Control
The NICE7000 supports parallel control of two elevators or group control of up to eight
elevators. It carries out elevator information exchange and processing through the CAN2
communication port, which implements coordination between multiple elevators to respond
to hall calls and improves the elevator use efciency.
The following table lists the parameters to be set for parallel/group control.
Table 5-5 Parameter setting of parallel/group control
Function
Code
Parameter
Name
Setting Range
Setting in Parallel
Control
Setting in Group
Control
Fd-00
Number of
elevators in
parallel/group
mode
1–8 2 3–8