- 172 -
•
In the driving state, increasing the value of F8-03 could reduce the rollback during the
elevator startup, but a very high value could cause car lurch at start.
•
In the braking state, increasing the value of F8-04 could reduce the jerk in command
direction during the elevator startup, but a very high value could cause car lurch at start.
Function Code Parameter Name Setting Range Default Unit Property
F8-05
Car load 0–255
0 - ●
This parameter is readable and reects the load situation in the car. The value is sampled
by the NICE7000
by using a load cell.
If F5-00 < 2, F8-05 = 0.
Function Code Parameter Name Setting Range Default Unit Property
F8-06 No-load load threshold 0–255 0 - ★
F8-07 Full-load load threshold 0–255 100 - ★
These two parameters respectively specify the car no-load and full-load thresholds.
Generally, the system automatically determines the values after load-cell auto-tuning. Adjust
them properly according to requirements.
Example:
If the load cell data is 25 and 175 respectively at no-load and full-load, the system
determines that the normal load range is 25–175.
Set F8-18, F8-19, and F8-20 respectively to 30%, 80%, and 110%.
When F8-05 is 70 [30% x (175-25) + 25 = 70), 145, and 190, the system determines that the
elevator is in light-load, full-load, and overload state.
If F8-06 = F8-07, the full-load and overload functions become invalid.
Function Code Parameter Name Setting Range Default Unit Property
F8-08
Anti-nuisance function 0, 1, 2, 4
0 - ☆
It is the criteria for judging whether nuisance exists.
The values are as follows:
•
0: Anti-nuisance function disabled
•
1: Nuisance judged by load cell
A load cell is required. The system judges whether nuisance exists by comparing the
load cell data and the number of car calls.
•
2: Nuisance judged by light curtain
The system determines that nuisance exists when the light curtain does not act after the
elevator stops at arrival for three consecutive times.