EasyManua.ls Logo

MSA SUPREMATouch - Page 143

MSA SUPREMATouch
309 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SUPREMATouch
142
Installation
MSA
US
Configuration of MCI 20
No configuration
Configuration of MCI 20 BFE
No configuration
Configuration of the MAT Module
Two solder bridges are provided for each input on the bottom of the circuit board for 3 or 5 wire
operation of the sensors:
NOTE: The solder bridges for 3 wire operation must be closed only when passive sensors
(MPI module) are connected. For 5 wire operation with active sensors (MCI module), the solder
bridges must be open!
WARNING
Passive sensors should never be connected to an MCI module, as this may cause the destruc-
tion of the sensors and/or the MAI/MCI modules.
Solder bridge OPEN = 5 wire operation
Solder bridge CLOSED = 3 wire operation
Assignment: BR1, BR2 input 1
BR3, BR4 input 2
BR5, BR6 input 3
BR7, BR8 input 4
BR9, BR10 input 5
BR11, BR12 input 6
BR13, BR14 input 7
BR15, BR16 input 8

Table of Contents