Installation
SUPREMATouch
155
US
Settings/Measure points/Alarms
Configuration of the MSI Module
S101 Code Switch
Fig. 84 View of the MSI Module
Configuration in the SUPREMA menu
Settings/Measure points/Sensor data
Settings/Measure points/Alarms
1st alarm/level 30.00
Above alarm level Alarm
Below alarm level No Alarm
Latching Alarm latching
2nd to 4th alarm de-activated
2nd 4th level de-activated
Sensor MSI
Measuring range 0 ... 100
Units any
1st alarm/level 30.00
Above alarm level Alarm contact s hut
Below alarm level Alarm contact open
Latching Alarm latching
2nd to 4th alarm de-activated
2nd 4th level de-activated